A wire break (loss of continuity) has been detected or reported in phase B of the motor connection, either within the drive or at the terminal. This critical fault means one of the motor phases is open-circuited. Attempting to operate the motor with a phase break can lead to severe damage to both the motor and the drive due to unbalanced currents.
Click steps to track your progress.
Power down the drive and motor, then measure the resistance of the motor cable phase B (e.g., from drive terminal V to motor terminal B/T2) using an ohmmeter to confirm continuity.
Disconnect the motor cable from both the drive output (V) and the motor input (B/T2), then visually inspect and retighten all connections.
Measure the resistance of the motor windings (e.g., U-V, V-W, W-U) at the motor terminals; an open circuit on one phase (e.g., V-U infinite, V-W infinite) indicates an internal motor fault.
If a motor contactor is used, check its contacts for continuity across phase B (e.g., terminals 3-4) with the contactor energized and de-energized.
Temporarily swap the motor phase B and C connections at the drive (connect motor Phase B cable to drive W, motor Phase C cable to drive V) and observe if the fault shifts to 'Wire break in phase C'.