4640

Drive initialization

Beckhoff · TwinCAT 2 NC

What does 4640 mean?

The drive has not been fully initialized after being created in the system. This indicates that subsequent critical steps, such as I/O initialization, drive parameterization, and a system reset, have not been performed. Without complete initialization, the drive cannot enter an operational state and will not respond to motion commands.

Common Causes

  • New drive installation where the mandatory initialization routine (e.g., parameter upload, I/O mapping, axis assignment) has not been completed.
  • Firmware update failure or incomplete firmware flash, leaving the drive in an uninitialized or partially configured state.
  • Factory reset command executed without subsequent reloading of a valid parameter set, resulting in default or invalid settings.
  • PLC or control system failing to send the required initialization commands or valid axis parameters during startup communication.
  • Corrupted non-volatile memory preventing the drive from loading its default or stored configuration upon power-up.

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    Connect to the drive with the commissioning software and perform a full parameter upload from a known good configuration file, then save to non-volatile memory.

  2. 2

    Execute a full drive reset (e.g., via parameter P0-01 = 1 or a specific reset command) to ensure the new parameters are applied.

  3. 3

    Verify that all required I/O mappings (e.g., digital inputs DI1-DI8, analog inputs AI1-AI2) are correctly configured in the drive's I/O parameter group (e.g., P7-xx).

  4. 4

    Check the communication link between the PLC/controller and the drive to ensure initialization commands are being received (e.g., monitor communication status bits or frames).

  5. 5

    If applicable, re-flash the drive firmware to the latest stable version according to the manufacturer's instructions.

Browse all codes in this manual (60)
Verified technical data. Last updated: April 2026

Related Faults

4000Internal error4001Memory error4002Nc retain data error (persistent data)