Bosch Rexroth · IndraDrive C Drive Controllers
The DC bus voltage in the drive's power section has exceeded its maximum allowable limit. This is typically caused by regenerated energy from the motor that cannot be dissipated.
Click steps to track your progress.
Verify the braking resistor connections and measure its resistance to ensure it is within specifications. Check for an open circuit.
Check the braking resistor's power rating and ensure it is adequately sized for the application's regenerative energy.
Increase deceleration ramps (longer braking times) in the motion profile to reduce the peak regenerative energy.
Check the functionality of the internal braking chopper. If the fault persists, it may indicate a defective drive.