Danfoss · VLT HVAC Drive High Power
A ground fault has been detected in the system, meaning current is flowing to earth through an unintended path. This is a critical safety issue that can cause electrical shock, equipment damage, or fire if not immediately addressed.
Click steps to track your progress.
Disconnect main power supply to the frequency converter at the upstream breaker. Verify zero voltage at L1, L2, L3 terminals.
Disconnect the motor cables (U, V, W) from the frequency converter output terminals (T1, T2, T3).
Measure insulation resistance from each motor phase (U, V, W) to motor frame ground using a megohmmeter (e.g., 500VDC or 1000VDC).
Measure insulation resistance from each motor cable conductor (T1, T2, T3) to earth ground (cable shield/conduit) with the motor disconnected.
Visually inspect the motor cable along its entire length for signs of damage to the outer jacket or inner insulation.
If insulation resistance is below acceptable limits (e.g., < 1 Megohm), isolate the faulty component (motor or cable) and replace.