Danfoss · VLT HVAC Drive High Power
The control board EEPROM data is defective or too old. This indicates a corruption or obsolescence of the non-volatile memory storing control board parameters.
Click steps to track your progress.
1. Back up all parameters from the frequency converter (if accessible via control panel or software).
2. Perform a factory reset of the control board parameters (e.g., Parameter P14-22 Load defaults) to clear potentially corrupted data.
3. Download the backed-up parameters to the frequency converter after the factory reset.
4. Power cycle the frequency converter (main input power off for 5 minutes) to ensure a complete system reboot.
5. Verify the frequency converter's firmware version is up-to-date and compatible with any recent changes or system updates.