Danfoss · VLT HVAC Drive High Power
The motor current parameter (parameter 1-24) entered for the Automatic Motor Adaptation (AMA) is set too low for the connected motor. This incorrect setting can lead to inaccurate motor modeling during AMA, resulting in suboptimal drive control and potential misoperation or reduced performance.
Click steps to track your progress.
1. Increase Parameter P1-24 (Motor Current) to precisely match the motor nameplate FLA.
2. Verify motor winding resistance across all three phases (U-V, V-W, W-U) using an ohmmeter (readings should be balanced within 5%).
3. Check for secure connections at the motor terminal block and drive output terminals (U, V, W).
4. Measure actual motor current with a clamp meter during a light load test run (if possible) and compare to drive's current display.
5. If problem persists after correcting P1-24, consider performing a drive factory reset and re-entering all parameters.