58

AMA internal fault (Contact supplier)

Danfoss · VLT HVAC Drive High Power

What does 58 mean?

A persistent internal fault has occurred during the Automatic Motor Adaptation (AMA) process that cannot be resolved through simple restarts. This indicates a potentially deeper issue with the drive's internal diagnostics or hardware.

Common Causes

  • A critical internal drive hardware component has failed (e.g., main processor, power module, measurement circuit).
  • Severe and unrecoverable corruption of drive firmware or operating system.
  • Permanent damage to the control board or its communication bus.
  • Persistent internal sensor fault preventing accurate motor characterization.
  • Failure of a power stage component that impacts motor current or voltage output during AMA.

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    1. Record all drive parameters (P-settings) for documentation and future reference before further troubleshooting.

  2. 2

    2. Cycle power to the drive (power off, wait 60 seconds, power on) and observe if the fault persists immediately.

  3. 3

    3. Disconnect the motor completely from the drive output terminals (U, V, W) and attempt AMA in 'no motor connected' mode (if supported).

  4. 4

    4. Visually inspect the drive's internal components for signs of burning, bulging capacitors, or physical damage.

  5. 5

    5. Collect drive model number, serial number, firmware version, and detailed fault occurrence information for technical support.

Browse all codes in this manual (60)
Verified technical data. Last updated: April 2026