Danfoss · VLT HVAC Drive High Power
The motor current has exceeded the value set in parameter 4-18 (Current Limit). This indicates that the motor is drawing excessive current, potentially due to overload, incorrect motor data, or a mechanical issue, which could lead to motor or drive overheating and damage if not addressed.
Click steps to track your progress.
1. Measure the motor current with an external clamp meter and compare it to the drive's displayed current (e.g., P16-04).
2. Verify Parameter P4-18 (Current Limit) is set appropriately, typically 150-180% of nominal motor current (P1-24).
3. Disconnect the motor from the mechanical load and check for free rotation of the motor shaft by hand.
4. Measure motor winding resistance and insulation resistance (megohmmeter) to detect internal motor faults.
5. Increase Parameter P2-10 (Acceleration Ramp 1) to a longer duration to reduce inrush current during startup.
6. Confirm incoming AC line voltage (L1, L2, L3) at the drive input terminals is balanced and within specification.