Danfoss · VLT HVAC Drive High Power
An external interlock, configured to stop the drive, has been activated via a digital input. This prevents the drive from operating until the interlock condition is cleared and a reset signal is sent, ensuring safety or process integrity.
Click steps to track your progress.
1. Identify the specific digital input (e.g., DI1, DI2) configured as an interlock using parameters P5-10 to P5-15.
2. Monitor the status of the identified digital input in the drive's monitoring menu (e.g., P16-20) to confirm its active state.
3. Trace the wiring from the digital input terminal back to the interlock device (e.g., limit switch, safety relay).
4. Verify the physical state of the interlock device (e.g., check if a guard is open, if an E-stop button is pressed).
5. Confirm the digital input parameter (e.g., P5-10) is correctly set for the desired logic (e.g., Normally Open/Normally Closed).
6. Test the external interlock device and its wiring for continuity with a multimeter to ensure proper operation.