The frequency converter's output frequency has reached or exceeded the maximum value set in parameter 4-19 (Max Output Frequency). This typically occurs when the drive is commanded to run faster than its configured limit, potentially indicating an over-speed condition or an incorrectly set limit for the application.
Click steps to track your progress.
1. Increase Parameter P4-19 (Max Output Frequency) to the desired maximum operating frequency, considering motor and mechanical limits.
2. Identify the active speed reference source (e.g., P3-00) and verify its scaling parameters (e.g., P3-03, P3-04 for analog input).
3. Monitor the active speed reference value in the drive's display (e.g., P16-00) and compare it to P4-19.
4. Adjust the external speed command source (e.g., potentiometer, PLC analog output) to prevent exceeding the drive's maximum limit.
5. If a PID controller is active, review its setpoint and tuning parameters (e.g., P7-30 to P7-35) to prevent overshoot or excessive output.