Danfoss · VLT HVAC Drive High Power
The motor thermistor indicates an overtemperature condition, or it may be disconnected. The frequency converter can be configured to issue either a warning or an alarm based on parameter 1-90 Motor Thermal Protection. This fault protects the motor from thermal damage.
Click steps to track your progress.
Verify the motor temperature using an external non-contact thermometer to confirm actual overtemperature.
Measure the resistance of the motor thermistor at the frequency converter's thermistor input terminals (e.g., 53/54, or specific AIN) and compare to its datasheet values.
Check the wiring continuity and connections of the thermistor cable from the motor to the frequency converter.
Inspect the motor's cooling fan and cooling fins for blockages or damage.
Review parameter P1-90 (Motor Thermistor Function) to ensure it is correctly enabled and configured for the thermistor type.
Reduce the mechanical load on the motor or verify its sizing for the application.