The motor's torque has exceeded the value set in parameter 4-16 Torque Limit Motor Mode or the generator torque limit in parameter 4-17 Torque Limit Generator Mode. This condition can be a warning or escalate to an alarm and trip, protecting the mechanical system from excessive stress.
Click steps to track your progress.
Monitor the motor torque (parameter 16-15 Motor Torque) on the frequency converter display during operation.
Inspect the mechanical system for any obstructions, jamming, or excessive friction that would increase load.
Increase the torque limit values in P4-16 (Torque Limit Motor Mode) and P4-17 (Torque Limit Generator Mode) gradually, if the mechanical system allows.
Increase acceleration ramp time (P3-41 for ramp 1) to reduce peak torque during startup.
Verify motor nameplate data (kW, V, A, Hz, RPM) against the frequency converter's motor setup parameters (P1-03 to P1-07).
Check for proper mechanical alignment of shafts, couplings, and bearings.