Danfoss · VLT HVAC Drive High Power
There is a short circuit condition present in the motor or its wiring. This is a critical fault that can lead to immediate damage of the frequency converter's output stage if not quickly resolved.
Click steps to track your progress.
Disconnect main power supply to the frequency converter at the upstream breaker. Verify zero voltage at L1, L2, L3 terminals.
Disconnect the motor cables (U, V, W) from the frequency converter output terminals (T1, T2, T3).
Measure insulation resistance between motor phases (U-V, V-W, W-U) and from each phase to motor frame ground using a megohmmeter (500VDC).
Measure continuity and insulation resistance of the motor cables from drive terminals to motor terminals.
Visually inspect motor cables for signs of physical damage, chafing, or signs of overheating along their entire length.
If motor or cable insulation resistance is below 1 Megohm, isolate and replace the faulty component.