Danfoss · VLT HVAC Drive High Power
The signal on one of the analog inputs is less than 50% of the programmed minimum value. This condition, appearing if parameter 6-01 Live Zero Timeout Function is programmed, often indicates broken wiring or a faulty sensor/device sending the analog signal, risking incorrect operation or control.
Click steps to track your progress.
Verify the analog input signal at the sensor output terminals using a multimeter (e.g., set to mA or VDC).
Measure the analog input signal directly at the frequency converter's input terminals (e.g., terminal 53 to 55) to confirm signal presence.
Inspect wiring for continuity and secure connections from the sensor to the frequency converter's analog input terminals.
Check parameter 6-01 (Live Zero Timeout Function) to ensure it is correctly configured for the sensor type and application.
Review parameter 6-10 (Low Reference) and 6-11 (High Reference) settings to accurately match the sensor's output range.
Replace the analog input sensor if its output consistently remains below the expected live zero despite proper wiring.