Danfoss · VLT HVAC Drive High Power
No motor is connected to the output of the frequency converter. This prevents motor operation and could indicate a wiring issue or incorrect system setup.
Click steps to track your progress.
Visually inspect the motor cable connections at both the frequency converter output (U, V, W) and the motor terminal box.
Measure the resistance between the U, V, W output terminals of the frequency converter (with power off) to confirm motor winding continuity.
Verify motor nameplate data against frequency converter parameters P1-03 (Motor kW), P1-04 (Motor V), P1-05 (Motor A), P1-06 (Motor cos phi), P1-07 (Motor Speed).
Check for an open circuit within the motor windings by measuring resistance directly at the motor terminal box.
Perform an Automatic Motor Adaptation (AMA) via parameter P8-10 (Auto Adapt) to allow the frequency converter to characterize the connected motor.