ALARM 36

Mains failure

Danfoss · VLT HVAC Drive High Power

What does ALARM 36 mean?

The supply voltage to the frequency converter is lost. This warning/alarm is active only if parameter 14-10 Mains Failure is not set to [0] No Function. This causes a complete loss of power to the drive and connected motor.

Common Causes

  • Complete loss of incoming three-phase (or single-phase) AC supply voltage to the frequency converter input terminals.
  • Tripped upstream circuit breaker, blown fuse, or open motor protection switch in the main power circuit.
  • Loose or corroded connections in the input power path (e.g., main contactor, input reactor, terminal blocks).
  • Significant and prolonged voltage sag below the frequency converter's undervoltage trip threshold (e.g., below 340V AC for 400V drive).
  • Faulty internal voltage sensing circuit in the frequency converter, incorrectly detecting a mains failure.

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    1. Measure the incoming AC line voltage (L1, L2, L3) at the frequency converter input terminals (e.g., R, S, T) using a multimeter.

  2. 2

    2. Inspect and reset any tripped upstream circuit breakers, blown fuses, or motor protection switches in the input power circuit.

  3. 3

    3. Check the tightness of all input power wiring connections at the frequency converter and any upstream isolation devices.

  4. 4

    4. Review parameter P14-10 Mains Failure setting to ensure it's configured for the desired response to power loss (e.g., [0] No Function).

  5. 5

    5. Monitor the AC supply voltage with a power quality analyzer to detect intermittent power loss events or severe sags.