Danfoss · VLT HVAC Drive High Power
The supply voltage to the frequency converter is lost. This warning/alarm is active only if parameter 14-10 Mains Failure is not set to [0] No Function. This causes a complete loss of power to the drive and connected motor.
Click steps to track your progress.
1. Measure the incoming AC line voltage (L1, L2, L3) at the frequency converter input terminals (e.g., R, S, T) using a multimeter.
2. Inspect and reset any tripped upstream circuit breakers, blown fuses, or motor protection switches in the input power circuit.
3. Check the tightness of all input power wiring connections at the frequency converter and any upstream isolation devices.
4. Review parameter P14-10 Mains Failure setting to ensure it's configured for the desired response to power loss (e.g., [0] No Function).
5. Monitor the AC supply voltage with a power quality analyzer to detect intermittent power loss events or severe sags.