Danfoss · VLT HVAC Drive High Power
The DC-link voltage has exceeded its limit, causing the frequency converter to trip after a certain time. This often occurs due to regenerative braking or excessive mains voltage, which can damage the inverter section if not mitigated.
Click steps to track your progress.
Measure the incoming AC mains voltage (L1-L2, L2-L3, L3-L1) and confirm it is within the frequency converter's specified operating range.
Increase the deceleration ramp time (P3-42 for ramp 1, P3-44 for ramp 2) to allow for slower energy dissipation.
Verify the connection and resistance of the external braking resistor (if present) and ensure it matches the value specified in P2-11 (Brake Resistor Ohms).
Consider implementing a brake chopper and resistor combination or a regenerative front end for high inertia applications.
Review the application for external forces causing motor regeneration, such as overhauling loads or rapid changes in load direction.