Danfoss · VLT HVAC Drive High Power
The DC-link voltage has dropped below the undervoltage limit. If no 24V DC back-up supply is connected, the frequency converter will trip after a fixed time delay (varying by unit size). This indicates insufficient input power, which can lead to uncontrolled motor shutdown.
Click steps to track your progress.
Measure the incoming AC mains voltage (L1-L2, L2-L3, L3-L1) at the frequency converter's input terminals to confirm stable supply.
Check all upstream circuit breakers and fuses for tripped or blown conditions.
Inspect and tighten all mains input wiring connections (L1, L2, L3) at the frequency converter.
Verify the integrity of the 24V DC back-up supply (if installed) and its connection to the control card.
Monitor the DC-link voltage (parameter 16-01 DC Link Voltage) on the display to observe voltage behavior before a trip.