The control card's 10 V supply from terminal 50 is less than 10 V, indicating it is overloaded. This can affect connected sensors or potentiometers, leading to incorrect control signals or loss of functionality.
Click steps to track your progress.
Disconnect all external devices from terminal 50 and measure the voltage between terminal 50 and terminal 55 (common) using a multimeter.
Reconnect devices one by one to identify which device causes the voltage drop on terminal 50.
Inspect all wiring connected to terminal 50 for damage, short circuits, or incorrect connections.
Verify the current consumption of each connected device (e.g., sensor, potentiometer) to ensure the total load does not exceed the frequency converter's specified 10V output capacity (e.g., 15mA).
Replace any external device confirmed to be drawing excessive current from terminal 50.