Danfoss · VLT HVAC Drive High Power
The DC-link voltage is lower than the warning limit, which depends on the frequency converter's voltage rating. The unit remains active but operating at a reduced DC link voltage can affect motor performance or lead to an undervoltage trip.
Click steps to track your progress.
Measure the incoming AC mains voltage (L1-L2, L2-L3, L3-L1) under load and verify it is within the frequency converter's specified operating range.
Check for loose or corroded connections on the frequency converter's input terminals (L1, L2, L3).
Review the cable sizing for the mains supply to ensure it is adequate for the frequency converter's current rating and cable length.
Monitor the DC-link voltage on the frequency converter's display (parameter 16-01 DC Link Voltage) during operation to identify sag events.
Reduce the motor load or consider a higher-rated frequency converter if continuous low DC-link voltage is observed under normal operating conditions.