Fronius · Primo GEN24
The AC grid voltage at the inverter's connection point is too high, exceeding the permitted limits for the Fronius Primo GEN24 208-240 inverter. This condition can lead to the inverter disconnecting from the grid to protect itself and the system.
Click steps to track your progress.
Verify the AC grid voltage at the inverter's connection point using a multimeter and compare it with the Fronius Primo GEN24 208-240 inverter's specified operating limits.
Check the length and cross-section of the AC connection cable; ensure it is adequately sized for the distance and current to minimize impedance.
Inspect all AC connections for proper termination and secure contact.
Contact the grid operator to report excessively high grid voltage or high grid impedance issues in the local network.
If applicable, check inverter settings related to grid voltage limits to ensure they comply with local grid codes.