Fronius · Primo GEN24
The AC grid voltage at the inverter's connection point has fallen below the permitted limits for the Fronius Primo GEN24 208-240 inverter. This can cause the inverter to disconnect from the grid, preventing proper power feed-in.
Click steps to track your progress.
Measure the AC grid voltage at the inverter's connection point with a multimeter and confirm it falls within the Fronius Primo GEN24 208-240 inverter's specified operating range.
Examine the AC connection cable for appropriate length and cross-section; optimize if necessary to reduce impedance.
Confirm all AC connections are tight and correctly terminated to minimize voltage drop.
Contact the grid operator to investigate and resolve issues related to low grid voltage or high grid impedance in the local grid.
Check the grid connection point for other large loads that might be causing voltage sags.