141

BR1-Trip (Brake error, main axes)

Kuka · KR C2 Robot Controller

What does 141 mean?

This fault indicates an error in the brake system for the main axes (KPS-600). This could be due to a faulty brake component, incorrect brake control signals, or issues with the brake power supply, potentially compromising safety and the ability to hold the main axes.

Common Causes

  • BR1-Trip: Brake error detected on main axes (P1-22).
  • Mechanical brake failure on the primary axes.
  • Incorrect wiring or faulty connection to the main brake.
  • Control signal error for the main brake engagement.

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    Verify the brake control signal voltage at the brake terminals during activation and deactivation cycles.

  2. 2

    Measure the resistance of the brake coil for the main axes and compare it to specifications.

  3. 3

    Inspect the brake wiring and connectors for continuity and secure connection.

  4. 4

    Check for mechanical obstruction preventing brake release or engagement.

Browse all codes in this manual (58)