65

CE4-Trip (Drive bus communication errors exceeded)

Kuka · KR C2 Robot Controller

What does 65 mean?

This fault indicates that the maximum permissible number of communication errors with the drive bus has been exceeded. For KSDs, this also includes too many toggle bit errors in succession. This severe communication breakdown leads to short-circuit braking, signifying a loss of reliable control and data exchange with the drive bus.

Common Causes

  • CE4-Trip: Drive bus communication errors exceeded limit (P1-14).
  • Network cable issues (damaged, loose, or incorrect type).
  • Interference on the communication bus.
  • Faulty communication interface on the drive or network device.

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    Inspect the drive bus communication cable for physical damage along its entire length, including connectors.

  2. 2

    Verify the proper termination (resistor presence/absence) at both ends of the drive bus segment according to system specifications.

  3. 3

    Check parameter settings for communication speed and address for each device on the bus, ensuring they are unique and correct.

  4. 4

    Measure continuity of bus lines at communication terminals to detect open or short circuits.

Browse all codes in this manual (58)