Kuka · ProfiNet Controller/Device 3.1
The PROFINET connection between the PLC and the specified device ({Name}) could not be established within the configured timeout period. This can be caused by an excessively low bus timeout setting, a mismatch between the controller and PLC configurations, or a defective PROFINET device, preventing proper operation.
Click steps to track your progress.
Increase the 'Bus timeout' parameter setting in the PROFINET configuration on the robot controller (refer to Page 18) to allow more time for connection.
Verify that the PROFINET device configuration in WorkVisual on the robot controller matches the PROFINET configuration loaded in the PLC for device {Name}.
Perform diagnostics on the PROFINET device {Name} itself, potentially replacing it if internal faults are detected.