Lenze · 4800/4900 Series
This fault is triggered by an external safety circuit or monitoring device connected to the drive, indicating a condition outside the drive itself requires attention. By default, this critical condition triggers a full TRIP, inhibiting all ignition pulses and resetting the Ready signal, as it typically signifies an important external protective function has been activated. Manual reset is required.
Click steps to track your progress.
Identify the specific digital or analog input (e.g., DI1, AI1) configured as the external fault source in the drive parameters (e.g., P3-xx).
Check the status of the external device connected to that input (e.g., emergency stop button pressed, limit switch open).
Measure the voltage at the external fault input terminal (e.g., X1:10) on the drive; verify it matches the expected state (e.g., 24VDC for active, 0VDC for fault).
Inspect the wiring from the external fault device to the drive's input terminals for continuity and secure connections.
Temporarily bypass the external fault device (only for testing, with caution) by wiring a jumper across the input terminals to see if the fault clears.
Review the drive's event log for any correlated messages from the specific external fault input.