This fault indicates an open circuit or very high resistance in the field circuit of a DC motor, preventing or severely limiting current flow to the motor field winding. Without a proper field, a DC motor can become unstable or overspeed. By default, this critical condition triggers a full TRIP, inhibiting all ignition pulses and resetting the Ready signal, to prevent uncontrolled operation and potential damage. Manual reset is required.
Click steps to track your progress.
Perform a lockout/tagout procedure. Measure resistance across the DC motor field winding terminals (F1, F2) with the field cable disconnected; expect tens to hundreds of Ohms (refer to motor nameplate).
Measure continuity of each conductor in the field cable from drive output to motor terminals using a multimeter; expect < 0.1 Ohm.
Verify tightness of all field circuit connections at the drive, motor, and any intermediate junction boxes (e.g., torque to 2 Nm).
Check for a blown fuse or tripped circuit breaker in the field excitation circuit (if installed).
With the drive powered and safe, measure the actual field voltage (e.g., P5-01) and current output at the drive's field terminals and compare to motor nameplate data.