FCI

Field circuit interrupted

Lenze · 4800/4900 Series

What does FCI mean?

This fault indicates an open circuit or very high resistance in the field circuit of a DC motor, preventing or severely limiting current flow to the motor field winding. Without a proper field, a DC motor can become unstable or overspeed. By default, this critical condition triggers a full TRIP, inhibiting all ignition pulses and resetting the Ready signal, to prevent uncontrolled operation and potential damage. Manual reset is required.

Common Causes

  • Loose connection at DC motor field terminals (F1, F2) or drive field output terminals.
  • Broken conductor within the DC motor field cable due to fatigue or mechanical damage.
  • Internal open circuit in the DC motor field winding (e.g., broken coil, poor connection).
  • Blown field fuse or tripped field circuit breaker (if present) in the field excitation circuit.
  • Incorrectly set field voltage (e.g., P5-01) or field current limit (e.g., P5-02) preventing proper field excitation.

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    Perform a lockout/tagout procedure. Measure resistance across the DC motor field winding terminals (F1, F2) with the field cable disconnected; expect tens to hundreds of Ohms (refer to motor nameplate).

  2. 2

    Measure continuity of each conductor in the field cable from drive output to motor terminals using a multimeter; expect < 0.1 Ohm.

  3. 3

    Verify tightness of all field circuit connections at the drive, motor, and any intermediate junction boxes (e.g., torque to 2 Nm).

  4. 4

    Check for a blown fuse or tripped circuit breaker in the field excitation circuit (if installed).

  5. 5

    With the drive powered and safe, measure the actual field voltage (e.g., P5-01) and current output at the drive's field terminals and compare to motor nameplate data.

Browse all codes in this manual (31)
Verified technical data. Last updated: April 2026