EL
ErrorLib
Brands
||
  1. Home
  2. Lenze
  3. 4800/4900 Series
  4. PR1
About·Privacy·Terms

ErrorLib — Industrial Fault Code Library

Disclaimer: ErrorLib is an independent technical reference tool. While we aim for accuracy, always verify with the manufacturer’s official service manuals before performing maintenance on industrial equipment. ErrorLib is not affiliated with the brands listed.

PR1

Parameter set 1 defective

Lenze · 4800/4900 Series

What does PR1 mean?

This fault specifically indicates that user-defined parameter set 1, stored in the drive's memory, has become corrupted or is invalid. By default, this condition is configured as a Warning, meaning it alerts the operator and is logged, but it does not immediately inhibit pulses. Using a defective parameter set can lead to improper drive operation or damage.

Common Causes

  • Corruption of the internal memory block storing parameter set 1.
  • Interruption during the saving process of parameter set 1 (e.g., power loss while writing P9-98 = 1).
  • Attempting to load a parameter set 1 that is incompatible with the current drive's firmware version.
  • Degradation or failure of the drive's non-volatile memory associated with parameter set 1.

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    Attempt to load an alternative, known good parameter set (e.g., switch to parameter set 2 using P0-02 = 2).

  2. 2

    Try to reload parameter set 1 from an external backup file using the drive's configuration software.

  3. 3

    Manually re-enter critical parameters for set 1, starting with motor data (e.g., P1-01, P1-02, P1-03).

  4. 4

    Execute a factory reset specific to parameter set 1 if available, or reset all parameters (P9-97 = 1) and rebuild set 1.

  5. 5

    Save the currently active parameter values as a new parameter set to overwrite the corrupted area (e.g., P9-98 = 1).

Browse all codes in this manual (31)
Verified technical data. Last updated: April 2026

Related Faults

ACIarmature circuit interruptedCCrSystem faultCE0Communication Fault (Automation Interface)
Source: Lenze 4800/4900 Series
View Official PDFSearch more codes in this manual