Lenze · 4800/4900 Series
This fault indicates a problem with an analog encoder providing feedback to the drive, such as a broken wire, short circuit, or the encoder itself being faulty. By default, this critical condition triggers a full TRIP, inhibiting all ignition pulses and resetting the Ready signal, as accurate feedback is essential for stable and safe control. Manual reset is required.
Click steps to track your progress.
Power off the drive and disconnect the analog encoder cable at terminal X5.
Measure the voltage or current output directly from the encoder at its output terminals using a multimeter while manually rotating the encoder shaft.
Check continuity of each conductor and shielding in the encoder cable from the encoder to drive terminal X5 using a multimeter.
Verify the drive's analog input configuration parameters (e.g., P5-10 for input type, P5-11 for scaling minimum) match the encoder's specifications.
Inspect encoder wiring for proper shielding termination at the drive and encoder ends to minimize noise pickup.