Lenze · 4800/4900 Series
This fault indicates a problem with an encoder connected to terminal X9 on the drive. This could be due to wiring issues, a faulty encoder, or mechanical damage. By default, this critical condition triggers a full TRIP, inhibiting all ignition pulses and resetting the Ready signal, as encoder feedback at this input is crucial for motor control. Manual reset is required.
Click steps to track your progress.
Power off the drive and disconnect the encoder cable at terminal X9.
Check for +5VDC or +24VDC supply voltage at the encoder power pins of terminal X9 from the drive.
Use a multimeter to check for continuity of each signal wire (A, /A, B, /B, Z, /Z) and power supply lines from the encoder to the drive connector.
With an oscilloscope, observe the A, B, and Z encoder signals at the drive's X9 terminals while manually rotating the motor shaft. Look for clean square waves.
Verify P5-01 (Encoder type selection) matches the installed encoder (e.g., incremental, SSI, absolute).