Lenze · 4800/4900 Series
This fault indicates that the polarity of an analog input signal (e.g., set-value, feedback) is inverted or incorrect, causing the drive to interpret the signal incorrectly. By default, this condition triggers a full TRIP, inhibiting all ignition pulses and resetting the Ready signal, as incorrect polarity can lead to unstable or dangerous operation. Manual reset is required.
Click steps to track your progress.
Identify the specific analog input (e.g., terminal X7) or feedback (e.g., terminal X5) generating the fault.
Verify the physical wiring of the identified input/feedback against the drive's wiring diagram for correct polarity.
Check the relevant drive parameter for signal polarity (e.g., P6-03 for analog input 1 polarity, P5-03 for encoder rotation direction).
Apply a known positive test signal (e.g., +5VDC) to the input and observe the drive's measured value (e.g., using a diagnostic screen); if it reads negative, swap polarity.
If using a bipolar input (e.g., -10V to +10V), ensure the zero-crossing reference is correctly wired.