Lenze · 8200 Series
A communication error has occurred on CAN-IN2, meaning faulty data is being received or the communication is interrupted. Potential causes include loose bus module connections or issues with the transmitting device. This can lead to loss of control over devices connected to CAN-IN2.
Click steps to track your progress.
Verify the CAN-IN2 communication module is securely seated in its slot on the drive controller, checking for proper electrical contact.
Inspect the entire CAN-IN2 bus cable run for signs of damage, cuts, or crushed sections.
Measure the resistance across the CAN_H and CAN_L lines at the network's physical ends; it should be approximately 60 Ohms (two 120 Ohm terminators in parallel).
Confirm CAN-IN2 communication parameters, including baud rate (P8-11) and node ID (P8-12), are correctly set and consistent for all devices on the bus.
Check the shielding integrity and proper earthing of the CAN-IN2 bus cable to minimize EMI influence.