Lenze · 8200 Series
An external disturbance has been detected, activating a digital signal assigned to the TRIP-SET function (DCTRL1-TRIP-SET). This typically results from a LOW level at the signal source for this function, causing the controller to inhibit. Ignoring this can lead to system shutdown and operational delays.
Click steps to track your progress.
1. Identify the external device connected to the digital input assigned to DCTRL1-TRIP-SET (e.g., C0020 for DI1, C0021 for DI2).
2. Measure the voltage level at the specific digital input terminal configured as DCTRL1-TRIP-SET; it should be HIGH (e.g., 24VDC) when no fault is present.
3. Inspect the wiring to the DCTRL1-TRIP-SET input for continuity, loose connections, or damage.
4. Verify the operational status of the external safety device or sensor connected to this input.
5. Check drive parameter settings for the assigned digital input to ensure DCTRL1-TRIP-SET is the intended function.