ce7

CAN Remote Parameterization Error

Lenze · 8200 Series

What does ce7 mean?

A communication error has occurred during remote parameterization via the system bus (C0370), typically because a node is unresponsive or unavailable. This can also be caused by incorrect parameter set changeover configuration with application I/O. Such errors prevent remote configuration and control of the drive.

Common Causes

  • The target CAN node (slave device) is powered off, in an error state, or has an incorrect node ID (P8-02 or P8-12) preventing addressing.
  • Incorrect parameter set changeover configuration (e.g., P0-02, P0-03) preventing remote writing to parameter sets.
  • High network latency or intermittent communication issues preventing the completion of parameterization commands (C0370).
  • Corrupted parameter data transmitted over the CAN bus, leading to rejection by the slave device.
  • The remote parameterization tool or software (C0370) has incorrect settings for the target device or network.

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    Confirm the target CAN slave device is powered on, healthy, and its CAN node ID (P8-02 for CAN-IN1 or P8-12 for CAN-IN2) matches the remote parameterization request.

  2. 2

    Review parameter P0-02 (Parameter set source) and P0-03 (Parameter set changeover mode) to ensure they are configured to allow remote parameter writing.

  3. 3

    Verify the CAN bus cabling for integrity and proper termination to eliminate physical communication errors.

  4. 4

    Re-transmit the parameter data if it is suspected to be corrupted, possibly simplifying the data structure for testing.

  5. 5

    Check the settings of the remote parameterization tool (C0370), including the target device address and communication protocol, to ensure they are correct.