Omron · MX2 Inverter
This warning indicates that the parameter set for the frequency upper limit (A061) is configured to a value higher than the inverter's maximum allowed frequency (A004). This inconsistent setting may lead to unexpected operational limits or prevent the drive from reaching its full potential.
Click steps to track your progress.
Access parameter A061 (Frequency Upper Limit) and compare its value to A004 (Inverter Max Allowed Frequency).
Set A061 (Frequency Upper Limit) to a value equal to or less than A004 (Inverter Max Allowed Frequency). A common practice is to set A061 to match A004 for maximum allowable speed.
Confirm that the new setting for A061 is stored by powering the drive off and on, then verifying the parameter value again.
If the issue persists, perform a parameter reset to factory defaults (e.g., P0-01 set to "99") and then re-enter all necessary application parameters carefully.