This warning indicates that the frequency lower limit (A062) is set higher than the Multi-step speed reference 0 (A020) or the output frequency setting (F001). This creates a logical inconsistency where the minimum allowed frequency is greater than a programmed speed reference, potentially limiting operation.
Click steps to track your progress.
Access parameters A062 (Frequency Lower Limit) and A020 (Multi-step Speed Reference 0). Compare their values.
Adjust A062 (Frequency Lower Limit) to be less than or equal to A020 (Multi-step Speed Reference 0).
Alternatively, if the application requires A020 to be higher, increase A020 (Multi-step Speed Reference 0) to be equal to or greater than A062.
If F001 (Output Frequency) is causing the issue when A020 is active, monitor the actual output frequency and verify consistency with A020.
Save the parameter changes and power cycle the drive to confirm the settings are active.