Omron · MX2 Inverter
This warning occurs when the inverter's starting frequency (b082) is set higher than the defined frequency upper limit (A061). This configuration is contradictory and may prevent the inverter from starting or operating as intended within its defined frequency limits.
Click steps to track your progress.
Access parameters b082 (Starting Frequency) and A061 (Frequency Upper Limit). Compare their values.
Adjust b082 (Starting Frequency) to be less than or equal to A061 (Frequency Upper Limit).
Alternatively, if the application requires b082 to be higher, increase A061 (Frequency Upper Limit) to be equal to or greater than b082, ensuring A061 does not exceed A004 (Inverter Max Frequency).
Save the parameter changes and power cycle the drive to confirm the settings are active.
Initiate a start command and observe the drive's behavior to ensure it starts smoothly without the warning.