Omron · MX2 Inverter
This warning indicates that the inverter's starting frequency (b082) is set higher than the Multi-step speed reference 0 (A020) or the output frequency setting (F001). This creates a logical conflict for initial motor speed settings, potentially causing the drive to jump to a higher speed than intended immediately after starting.
Click steps to track your progress.
Access parameters b082 (Starting Frequency) and A020 (Multi-step Speed Reference 0). Compare their values.
Adjust b082 (Starting Frequency) to be less than or equal to A020 (Multi-step Speed Reference 0).
Alternatively, if the application requires b082 to be higher, increase A020 (Multi-step Speed Reference 0) to be equal to or greater than b082.
Save the parameter changes and power cycle the drive to confirm the settings are active.
Initiate a start command using Multi-step Speed Reference 0 and observe the drive's behavior to ensure a smooth transition.