Omron · MX2 Inverter
This warning occurs when the inverter's starting frequency (b082) is set higher than one or more of the defined multi-step speed references (A021-A035). This inconsistent parameter configuration may lead to unexpected speed behavior when switching between multi-step speeds, as the base speed is higher than a target speed.
Click steps to track your progress.
Access parameter b082 (Starting Frequency) and review all multi-step speed reference parameters A021 through A035.
Identify which specific multi-step speed reference(s) are lower than b082.
Adjust b082 (Starting Frequency) to be less than or equal to the lowest multi-step speed reference that might be selected for operation.
Alternatively, if the application requires b082 to be higher, increase the relevant A021-A035 multi-step speed references to be equal to or greater than b082.
Save the parameter changes and power cycle the drive. Then re-check the parameter values and test operation using the affected multi-step speed references.