This warning indicates that the inverter's starting frequency (b082) is set higher than the jogging frequency (A038). This inconsistency can cause an abrupt speed change when transitioning from a jog command or if jogging is initiated at startup, potentially leading to jerky motion or mechanical stress.
Click steps to track your progress.
Access parameters b082 (Starting Frequency) and A038 (Jogging Frequency). Compare their values.
Adjust b082 (Starting Frequency) to be less than or equal to A038 (Jogging Frequency).
Alternatively, if the application requires b082 to be higher for normal starts, increase A038 (Jogging Frequency) to be equal to or greater than b082.
Save the parameter changes and power cycle the drive to confirm the settings are active.
Initiate a jog command and observe the drive's behavior to ensure a smooth transition and correct jog speed.