Omron · MX2 Inverter
For the second motor settings, this warning indicates that the 2nd frequency lower limit (A262) is set higher than the 2nd Multi-step speed reference 0 (A220) or the output frequency setting (F001). This creates a logical inconsistency for the alternative motor profile's minimum speed, potentially restricting the operation of the second motor.
Click steps to track your progress.
Read the current values of parameter A262 (2nd frequency lower limit), A220 (2nd Multi-step speed reference 0), and F001 (Output frequency setting).
Adjust parameter A262 to be less than or equal to parameter A220, ensuring the lower limit is below the multi-step speed reference.
Alternatively, if the A220 multi-step speed reference is too low, increase A220 to a value greater than or equal to A262.
Store the new parameter values in the drive's memory and cycle power to the drive.