292

2nd Motor Free Setting V/f Frequency 7 Exceeds Lower Limit

Omron · MX2 Inverter

What does 292 mean?

For the second motor settings, this warning indicates that the seventh point of the free setting V/f curve (b112) is set higher than the 2nd frequency lower limit (A262). This creates an inconsistent lower boundary for the V/f characteristic for the second motor, potentially restricting the minimum V/f output.

Common Causes

  • Parameter b112 (Free setting V/f curve frequency point 7) for the second motor is set to a value higher than parameter A262 (2nd frequency lower limit).
  • The V/f curve's maximum frequency point (b112) is configured to exceed the allowed operational lower frequency for the second motor (A262).
  • An illogical setting where the highest point of the V/f curve (b112) is above the lowest allowed operational frequency (A262), creating a conflict.

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    Read the current values of parameter b112 (Free setting V/f curve frequency point 7) and parameter A262 (2nd frequency lower limit).

  2. 2

    Adjust parameter b112 to be less than or equal to parameter A262, ensuring the V/f curve point respects the lower frequency limit.

  3. 3

    Alternatively, if a higher operational lower limit is required, increase A262 to a value greater than or equal to b112.

  4. 4

    Store parameter changes to the drive's memory and reboot the drive.

Browse all codes in this manual (60)
Verified technical data. Last updated: April 2026

Related Faults

001Frequency Upper Limit Exceeded002Frequency Lower Limit Exceeded005Multi-step Speed Reference 0 Exceeds Max Frequency
Source: Omron MX2 Inverter
View Official PDFSearch more codes in this manual