For the second motor settings, this warning occurs when the seventh point of the free setting V/f curve (b112) is set higher than the 2nd Multi-step speed reference 0 (A220) or the output frequency setting (F001). This creates a conflict where the V/f curve's maximum frequency is inconsistent with a programmed speed reference for the second motor, potentially causing unintended speed limits.
Click steps to track your progress.
Read the current values of parameter b112 (Free setting V/f curve frequency point 7), A220 (2nd Multi-step speed reference 0), and F001 (Output frequency setting).
Adjust parameter b112 to be less than or equal to parameter A220, ensuring the V/f curve point does not exceed the multi-step speed reference.
If A220 or F001 are intended to operate at a higher frequency, increase these parameters to be greater than or equal to b112.
Save all modified parameters to the drive's memory and cycle power to the inverter.