This fault occurs when the Unattended Start Protection (USP) function is enabled and a Run command is present simultaneously with the application of power. It prevents the motor from unexpectedly starting upon power-up, requiring deliberate action to clear the fault and resume operation, enhancing safety.
Click steps to track your progress.
Ensure that all 'Run' commands (e.g., FWD, REV digital inputs) are OFF (low signal) before applying main power to the inverter.
Check the state of the digital input terminals (e.g., FWD, REV) using a multimeter to confirm they are at 0V (or logic low) when power is applied.
If using serial communication, verify that no 'Run' command is sent by the master device until after the inverter has fully initialized.
Disable the Unattended Start Protection function (Parameter P6-01 set to 0) if the application design permits and risks are acceptable.
Trace the control wiring for 'Run' commands to ensure no short circuits or faulty switches are maintaining an active signal.