Omron · MX2 Inverter
This fault indicates a ground fault detection between the inverter's output terminals and earth ground, typically during power-up tests. The inverter's protection system detects current leakage paths, tripping to prevent electric shock and damage to the motor or inverter.
Click steps to track your progress.
Disconnect all motor phases (U, V, W) from the inverter output terminals. Test insulation resistance between each output terminal and earth ground (PE) using a megohmmeter (insulation tester).
With motor cables disconnected from inverter, measure insulation resistance between each motor phase wire and the motor frame (PE) using a megohmmeter.
Visually inspect the motor terminal box and inverter output terminals for moisture, debris, or damaged insulation.
Verify the integrity and continuity of the earth ground (PE) connection from the inverter chassis to the main power panel.
If the fault clears with the motor disconnected, the ground fault is in the motor or motor cable; if it persists, the inverter has an internal ground fault.