Omron · MX2 Inverter
This fault is triggered when the inverter detects an excessive input voltage from the power supply, specifically during its idle (Stop) mode for a prolonged period (100 seconds). The inverter enters a fault state to protect its internal components from damage due to sustained high voltage.
Click steps to track your progress.
Measure the input AC voltage across inverter terminals L1, L2, L3 using a multimeter to confirm it is within the specified operating range (e.g., 380-480V for a 400V unit).
Monitor the input voltage over time to detect intermittent surges or sustained high voltage conditions using a logging multimeter or power quality analyzer.
Verify that the installed inverter's rated input voltage matches the facility's power supply voltage (e.g., a 400V class inverter for a 400V supply).
Check for loose or corroded connections at the inverter's input terminals L1, L2, L3 and in the upstream power distribution.
If sustained high input voltage is confirmed, consult with facility maintenance to investigate the upstream power supply and distribution transformer output.