Omron · MX2 Inverter
This fault occurs when there is a communication failure between the two internal CPUs within the inverter. Such a failure prevents coordinated operation and leads to an inverter trip, indicating a critical internal control issue.
Click steps to track your progress.
1. Cycle power to the inverter completely (remove main AC supply for at least 30 seconds), then reapply to reset internal CPUs.
2. Verify input supply voltage (VAC) stability at the inverter terminals (R, S, T) using a multimeter; check for significant sags or surges.
3. Inspect inverter grounding connections (PE terminal) for integrity and low impedance (typically <1 Ω to earth ground).
4. Isolate potential sources of EMI by temporarily disabling adjacent high-frequency switching devices or ensuring proper separation of power and control wiring.
5. If the error persists after power cycling, consider a firmware re-flash (if supported) or replacement of the inverter's control board.