EL
ErrorLib
Brands
||
  1. Home
  2. Omron
  3. MX2 Inverter
  4. E41
About·Privacy·Terms

ErrorLib — Industrial Fault Code Library

Disclaimer: ErrorLib is an independent technical reference tool. While we aim for accuracy, always verify with the manufacturer’s official service manuals before performing maintenance on industrial equipment. ErrorLib is not affiliated with the brands listed.

E41

Modbus Communication Error

Omron · MX2 Inverter

What does E41 mean?

This fault occurs when a Modbus communication timeout happens, typically when the inverter does not receive data within the period specified by the communication watchdog timer (C077). This often indicates a break in network communication or incorrect settings, causing the inverter to trip if 'trip' is selected as the error behavior (C076=00).

Common Causes

  • Incorrect Modbus communication parameters (e.g., C071 Baud rate, C072 Stop bits, C073 Parity, C074 Node address) mismatch between inverter and Modbus master.
  • Loose or damaged RS-485 communication cable (e.g., A/B twisted pair) between the inverter and the Modbus master.
  • Missing or incorrect termination resistors (typically 120 Ω) on the Modbus network, especially at the ends of the bus.
  • Modbus master device failure, incorrect polling logic, or timing issues causing timeouts.
  • Excessive electrical noise on the RS-485 bus causing data corruption or preventing reliable communication.

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    1. Verify Modbus communication parameters C071-C074 on the inverter match the Modbus master device settings exactly (baud rate, parity, stop bits, address).

  2. 2

    2. Inspect the RS-485 wiring (terminals S+, S- or A, B) for proper polarity, shorts, breaks, or loose connections along the entire bus.

  3. 3

    3. Check for correct 120 Ω termination resistors at both physical ends of the RS-485 bus, ensuring they are not missing or duplicated.

  4. 4

    4. Use an RS-485 analyzer or monitoring software to observe data traffic and identify communication errors, timeouts, or invalid frames on the bus.

  5. 5

    5. Temporarily disconnect other devices from the Modbus network to isolate if another device is causing interference or bus contention.

Browse all codes in this manual (60)
Verified technical data. Last updated: April 2026

Related Faults

001Frequency Upper Limit Exceeded002Frequency Lower Limit Exceeded005Multi-step Speed Reference 0 Exceeds Max Frequency
Source: Omron MX2 Inverter
View Official PDFSearch more codes in this manual