E60-E69

Option Errors (0 to 9)

Omron · MX2 Inverter

What does E60-E69 mean?

These faults indicate errors related to an installed option board (E60 corresponds to option error 0, E61 to option error 1, etc.). The specific meaning of the error depends on the type of option board connected to the inverter, and they are reserved for diagnosing issues with the functionality or communication of these optional modules.

Common Causes

  • Incorrect installation of the option board (e.g., not fully seated in its slot, wrong slot used, bent pins).
  • Hardware malfunction of the option board itself (e.g., damaged component, corrupted firmware on the board).
  • Incompatibility between the option board and the inverter's main firmware version or model.
  • Wiring fault to or from the option board (e.g., I/O expansion, communication card), causing signal integrity issues.
  • Incorrect parameter configuration for the option board (e.g., A6-xx Option card settings) preventing proper initialization.

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    1. Power down the inverter, wait for DC bus discharge, then physically inspect the option board's seating in its slot; ensure it is firmly connected.

  2. 2

    2. Identify the specific option board installed and consult its manual to understand the meaning of the triggered error code (E60-E69, often detailed in the option board's documentation).

  3. 3

    3. Verify all external wiring connected to the option board's terminals (e.g., I/O, communication lines) for integrity, correct polarity, and proper termination.

  4. 4

    4. Check for parameter settings related to the option board (e.g., A6-xx group) and ensure they are correctly configured according to the application and board type.

  5. 5

    5. If available, try swapping the option board with a known good spare to rule out hardware failure of the board itself.