Omron · MX2 Inverter
This fault indicates that the encoder connected for feedback has been disconnected, has a wiring error, or is of an unsupported type (e.g., not line driver output). Without valid encoder feedback, the inverter cannot perform accurate speed or position control, leading to a shutdown to prevent erratic motor behavior.
Click steps to track your progress.
Power down the drive and motor. Visually inspect the encoder cable for physical damage along its entire length and at both connection points (encoder and drive X1 terminal block).
Using a multimeter, measure the continuity of each individual wire in the encoder cable from the encoder connector to the drive's X1 terminal block. Verify resistance is below 1 Ohm.
Verify the encoder supply voltage at the encoder side with a multimeter (e.g., 5VDC or 24VDC). Check for correct voltage according to encoder specifications.
Confirm the encoder wiring matches the drive's terminal diagram (e.g., A to X1-1, B to X1-3, Z to X1-5). Correct any misconnections.
Check drive parameter P2-01 (Encoder Type) to ensure it is set correctly for the installed encoder (e.g., "0" for incremental line driver). Adjust if necessary.
If using an incremental encoder, verify correct termination resistor settings if applicable, especially for long cable runs.